60-Cycle Submersible Cable Selection

60-Cycle Submersible Cable Selection

Motor Fuse Copper Cable Size from Control Box to Motor (feet)
Conductor Size, AWG
Phase HP Volts/Hz Std
Fuse
Dual-
Element
Fuse
#14 #12 #10 #8 #6 #4 #2
Three
Phase
  230/60 45 20   285 450 690 1100 1740  
5 460/60 25 10 650 1140 1800 2760      
  230/60 70 30     300 470 740 1170 1840
7.5 460/60 35 15 440 810 1200 1880 2960    
  230/60 90 35       350 560 880 1390
10 460/60 45 20   610 950 1400 2240    
  230/60 125 50         385 605 950
15 460/60 60 25     650 920 1540 2420  
  230/60 175 70         290 450 710
20 460/60 90 35     485 685 1160 1800 2840
  230/60 200 80           370 580
25 460/60 100 40       560 980 1480 2320
  230/60 250 110             480
30 460/60 125 50         820 1270 1920
40   175 70           940 1420
50 460/60 225 90             1140
60   250 100             980
Single
Phase
5   80 35     140 220 340 540 8660
7.5 230/60 125 45       155 240 380 610
10   175 60         180 280 450
15   250 100         118 180 290

«»

Motor Fuse Copper Cable Size from Control Box to Motor (feet)
Conductor Size, AWG, MCM
Phase HP Volts/Hz Std
Fuse
Dual-
Element
Fuse
#0 #00 #000 #0000 #250 #300 #350
Three
Phase
40   175 70 2100 2600          
50   225 90 1680 2100 2850        
60   250 100 1410 1760 2300        
75   350 150 1180 1400 1880 2370      
100   450 175   1080 1460 1850 2100    
125 460/60 600 200     1160 1470 1700 2050  
150   600 250       1190 1390 1670 1950
175   700 250       1080 1260 1520 1770
200   800 275         1080 1300 1520
250   900 350           1080 1260
300   1200 500             1020

 

© Copyright 1997 - 2017 American Turbine